EV Charger Cable Selection Guide: AC and DC Charging Current Calculation and Cost Optimization

July 6, 2026 · Willdigits

Proper cable selection is a key factor in the construction cost, safety, and system stability of EV chargers. This guide explains how to calculate charging current and select suitable cables for AC and DC charging systems.

1. Charging Current Calculation

Single-phase charging (AC EV charger)

For a single-phase AC EV charger, the current calculation formula is:

I = P / (U × 0.85)

Three-phase charging (DC EV charger)

For a three-phase DC EV charger, the current calculation formula is:

I = P / (U × 1.732 × 0.85)

2. AC Charging Cable Selection

The table below shows reference cable selection for AC EV chargers.

Power

Input Current

RCD Breaker

Copper Cable (YJV)

Aluminum Cable (YJLV)

Phase

AC 3.5kW

≤19A

32A / 2P

3×4

3×6

Single-phase

AC 7kW

≤38A

40A / 2P

3×6

3×10

Single-phase

AC 14kW

≤75A

80A / 2P

3×10

3×25

Single-phase

AC 11kW

≤19A

32A / 3P/4P

5×4

5×6

Three-phase

AC 21kW

≤38A

40A / 3P/4P

5×6

5×10

Three-phase

AC 42kW

≤75A

80A / 3P/4P

5×10

5×25

Three-phase

3. DC Charging Cable Selection

3.1 Integrated DC Charger

The table below shows reference cable selection for integrated DC chargers.

Power

Input Current

RCD Breaker

Copper Cable (YJV)

Aluminum Cable (YJLV)

Phase

DC 7kW

≤38A

40A / 2P

3×6

3×10

Single-phase

DC 20kW

≤36A

40A / 3P/4P

3×10+2×6

3×16+2×10

Three-phase

DC 30kW

≤54A

63A / 3P/4P

3×16+2×10

3×25+2×10

Three-phase

DC 40kW

≤72A

80A / 3P/4P

3×25+2×10

3×50+2×25

Three-phase

DC 60kW

≤108A

125A / 3P/4P

3×50+2×25

3×70+2×35

Three-phase

DC 80kW

≤143A

160A / 3P/4P

3×70+2×35

3×95+2×50

Three-phase

DC 120kW

≤215A

250A / 3P/4P

3×95+2×50

3×120+2×70

Three-phase

DC 160kW

≤286A

315A / 3P/4P

3×120+2×70

3×185+2×95

Three-phase

DC 180kW

≤322A

350A / 3P/4P

3×150+2×120

2×(3×120+2×70)

Three-phase

DC 200kW

≤358A

400A / 3P/4P

3×185+2×95

2×(3×150+2×70)

Three-phase

DC 240kW

≤430A

500A / 3P/4P

3×240+2×120

2×(3×185+2×95)

Three-phase

DC 320kW

≤572A

630A / 3P/4P

2×(3×150+2×70)

2×(3×240+2×120)

Three-phase

DC 360kW

≤644A

800A / 3P/4P

2×(3×185+2×95)

2×(3×240+2×120)

Three-phase

DC 400kW

≤715A

800A / 3P/4P

2×(3×185+2×95)

2×(3×240+2×120)

Three-phase

3.2 Split-type DC Charging Power Cabinet

The table below shows reference cable selection for split-type DC charging power cabinets.

Power

Input Current

RCD Breaker

Main Input Cable

Main Line to Terminal Connection

Ground Cable

240kW

≤430A

500A, 3P/4P

ZR-YJV-0.6/1-3×240+2×120

1. DC output: ZR-YJV-22-0.6/1-2×95, one set of cables per charging terminal.

2. Auxiliary power: ZR-2×2.5mm², one set of cables per charging terminal.

3. Communication cable: 2×(RVSP-500V 2×1mm²), terminals connected in series and linked to the rectifier cabinet.

≥35mm² copper wire (for each grounding terminal)

360kW

≤644A

800A, 3P/4P

2×(ZR-YJV-0.6/1-3×185+2×95)

1. DC output: ZR-YJV-22-0.6/1-2×95, one set of cables per charging terminal.

2. Auxiliary power: ZR-2×2.5mm², one set of cables per charging terminal.

3. Communication cable: 2×(RVSP-500V 2×1mm²), terminals connected in series and linked to the rectifier cabinet.

≥35mm² copper cable

480kW

≤860A

2×500A, 3P/4P

2×(ZR-YJV-0.6/1-3×240+2×120)

1. DC output: ZR-YJV-22-0.6/1-2×95, one set of cables per charging terminal.

2. Auxiliary power: ZR-2×2.5mm², one set of cables per charging terminal.

3. Communication cable: 2×(RVSP-500V 2×1mm²), terminals connected in series and linked to the rectifier cabinet.

≥35mm² copper cable

600kW

≤1072A

3×400A, 3P/4P

3×(ZR-YJV-0.6/1-3×185+2×95)

1. DC output: ZR-YJV-22-0.6/1-2×95, one set of cables per charging terminal.

2. Auxiliary power: ZR-2×2.5mm², one set of cables per charging terminal.

3. Communication cable: 2×(RVSP-500V 2×1mm²), terminals connected in series and linked to the rectifier cabinet.

≥35mm² copper cable

720 kW

≤1287 A

3×500 A, 3P/4P

3×(ZR-YJV-0.6/1-3×240+2×120)

1. DC output: ZR-YJV-22-0.6/1-2×95, one cable set per charging terminal.

2. Auxiliary power: ZR-2×2.5mm², one cable set per charging terminal.

3. Communication cable: 2×(RVSP-500V 2×1mm²), terminals connected in series to the rectifier cabinet.

≥35mm² copper cable

960 kW

≤1716 A

4×500 A, 3P/4P

4×(ZR-YJV-0.6/1-3×240+2×120)

1. DC output: ZR-YJV-22-0.6/1-2×95, one cable set per charging terminal.

2. Auxiliary power: ZR-2×2.5mm², one cable set per charging terminal.

3. Communication cable: 2×(RVSP-500V 2×1mm²), terminals connected in series to the rectifier cabinet.

≥35mm² copper cable

4. Charging station construction cost optimization

Cable costs account for a significant portion of EV charging station infrastructure investment, and optimizing cable design can significantly reduce total project costs.

Willdigits offers a neutral-free wiring solution, eliminating the need for a neutral conductor in certain configurations, reducing cable material usage and overall construction costs while maintaining compliance and safety.

5. Conclusion

Precise cable selection based on charging power and system topology ensures safe, efficient, and cost-effective deployment of EV charging stations. By optimizing design solutions, operators can significantly reduce infrastructure investment while maintaining high performance.